Hold-Test Drop %, Criteria & Pass/Fail

Methodology — window, criteria, deltas

Understand drop % vs criteria %, rising and stable holds, delta colours, and minimum test pressure checks before sign-off.

8 min readEngineer · Witness / QA

Test window

You define the hold period by selecting start and end on the pressure chart. All change and delta calculations use samples inside that window.

Overall pass/fail

  • Falling hold (↓): pass when drop ≤ criteria %.
  • Rising hold (↑): pass when rise ≤ criteria %.
  • Stable hold (—): pass when |change| ≤ criteria %.
  • Optional: pressure must stay at or above nominal test pressure for the full window when that check is enabled.
  • Red delta checkpoints can fail the test on any hold direction.

Hold direction

↑ means net pressure rose during the window; ↓ means it fell; — means the change was very small relative to start pressure.

A warming system often produces a rising hold—the app shows rise % instead of a misleading negative drop %.

Delta checkpoint colours

  • Green: this step’s |Δ| is not steeper than the previous step.
  • Red: the interval rose on a falling hold, fell on a rising hold, or the |Δ| magnitude grew compared with the step before.
  • A red delta checkpoint can fail the test on any hold direction.

Temperature

When the logger exports temperature, review the trace beside the chart. Cooling can look like a leak; warming can explain a rising hold.

Optional temperature-adjusted drop affects pass/fail only if you enable it and your procedure allows it.

Procedure first

PressureTrend helps you read a hold test; your written procedure, client specification, and code rules govern sign-off when they differ from the app.